a
a a
a
a
a
        Humidifan Bathroom (and toilet) Fan HF100 240V
a
 

The Humidifan series of automatic extract fans are designed for the specifier and contract user and, though competitively priced, offer many features only available on more expensive extract fans.

Three notable features are: ball bearing motor, auto reset thermal cut out and a lifetime guarantee on the sensor head. This model can be upgraded to an advanced Real Time data logging Datamatic fan system.

 
a
a
 

Special Features

  • Lifetime guarantee on the humidity sensor head
  • Three year guarantee
  • Ball bearing fan motor
  • Integral or remote humidity sensor
  • Auto reset thermal cut out fuse on fan motor
  • Night time set back to inhibit fan running in the silent hours
  • Silent integral mechanical backdraught shutters
  • Manual over-ride on switch
  • Wall, window or ceiling fit
  • Anticipatory response humidity sensor
  • Can be upgraded to Datamatic 100 Real Time data logging fan with remote humidity sensor
  • Complies with Building Regulations
  • Quiet running
  • Range of accessories
  • Full technical back up
Operation
Under the control of a microprocessor, the sensor monitors continuously the Relative Humidity (RH) in the room. If there is a sudden rise in the RH, the sensor anticipates hitting the set point and activates the fan before it is reached. After the fan has reduced the RH to about 5% below the preset set point, the fan switches off. When the fan is running under sensor and microprocessor control the L.E.D. flashes.

The user can override the automatic monitoring by pulling the cord. In this override on mode, the red L.E.D. lights continuously. This shows the user that the fan is under manual operation. When the cord is pulled again, the sensor and microprocessor take back control of the fan.
 
a
a Construction
The Humidifan combines stylish attractive case design with advanced electronic automatic controls. The motor is double insulated and is of the shaded pole type mounted on self-lubricating ball-bearings. The motor incorporates an overload protection device and conforms to EEC Directive 78-889 for radio interference. It will operate in ambient temperatures of up to 40°C. The fan complies to BS3456, BS800 and BS5490. The unit incorporates an electronic humidity sensor.

Installation
The modular concept of the fan makes it easy to install in a WALL, CEILING or WINDOW.
WALL: easily installed with a wall venting kit comprising a wall sleeve and outside wall grille.
CEILING: time saving, optional ceiling ring available for fitting into plasterboard. 100mm flexible ducting.
WINDOW: single pane or sealed unit easily installed with window kit.

In many instances, a passive air vent, or an air brick, may need to be fitted to other cooler rooms within the property, in order to promote a good airflow throughout the dwelling.

Fitting Kits available:
WALL: Comprises wall sleeve and external grille (available in brown, terracotta, buff or white)
WINDOW: Mounting unit suitable for S/G or D/G windows. For greater efficiency we would recommend that a fan and remote sensor configuration of this model be used for this application, order code HF100/REM/G100.
CEILING: Ceiling ring available for fitting into plasterboard. 100mm dia. ducting will be required. We only recommend that this axial fan be ducted a maximum 1.5 metres. For greater distances, a centrifugal or mixed flow type unit would be more appropriate. (see Centramatic and remote sensors data sheet)
a a
a
a
a

Order Codes

HF100 Fan with intergral humidity sensor
HF100/REM Kit comprising fan and separate humidity sensorr
HF100T/REM Kit comprising fan and separate humidity sensor/timer
HF100T With timed over-run for integral bathrooms and toilets (no humidity sensor)
W100 Wall fixing kit
G100 Window fixing kit
C100 Ceiling fixing kit
HF4 100mm fan only
HF4 PC 100mm fan with pull cord
HF4T 1000mm fan with timer
a
  a  
FAN DIMENSIONS
Casing (mm) A B C D E
  164mm 154mm 42mm 46mm 98mm
 
Hole Diameters (mm) Walls 107
Windows 130
  Ceilings 107
FAN TECHNICAL DATA
Insulation Double insulated
Voltage 240
Power 15 watts
Extract capacity 85 Cubic m/hr, 23 litres/sec
Pressure mm H20 3.4
dB (A) 38
HUMIDITY SENSOR TECHNICAL DATA
Set point (at manufacture) to activate the fan approaching 67% RH at 20°CC
Night time setback

1% increase in set point for every 1°C below 20°C

 
 
  © Airtech Environmental Systems 2007 |  Site Map  |  Privacy Statement  |  Terms of Use  |